1 · Basis of design
Process, media, release scenarios, zone classification, ventilation, existing installation and the operator's own requirements.
Services
Engineering is the part of a project that decides whether the equipment works. We start from the process and the risk assessment, not from a product list.
How we work
A gas detection concept answers four questions before any equipment is named: where could a release come from, where would it go, what has to be measured and at which threshold must something happen. From those answers follow the detection technology, the number and position of the measuring points, the mounting height relative to the density of the gas, and the ventilation assumptions the whole concept depends on.
The same applies to instrumentation. Whether a flow measurement holds its stated accuracy is decided by the primary element, the straight inlet run and the impulse lines — not by the transmitter datasheet. We check those conditions before quoting a device, because an instrument installed into unsuitable conditions is an expensive way to generate wrong numbers.
The deliverable is a written concept: equipment list, positions, signal paths, alarm logic and the documentation the operator needs for approval and for the next audit.
Sequence
Process, media, release scenarios, zone classification, ventilation, existing installation and the operator's own requirements.
Technology selection per measuring point, number and position of points, thresholds and alarm logic, signal path to the controller and the control system.
Device selection, configuration, materials and process connections, approval situation, spare parts and consumables over the service life.
Concept, equipment list, positions, wiring and the records the operator has to keep for the approval and for the audit.
FAQ
If the measuring points, thresholds, signal paths and documentation are already defined, no — then it is a supply order and we quote it as one. If the device list came from a catalogue rather than from a concept, a short engineering step almost always changes the quantity, and usually downwards.
Yes, and it is the right starting point. The gas detection concept has to be consistent with the explosion protection document and the risk assessment rather than parallel to them.
Enquiry
Send us your requests with technical specifications to receive a prompt reply from our industry specialists. For gas detection, add the gases and the zone classification.
Or by email: purchasing@vertex-group.de